CyberPower 6000VA/5400W Online UPS
₱112000
Model | OLS6000E |
Capacity(VA/W) | 6000VA / 5400W |
Typology | Online (Double Conversion) |
Energy-Saving Technology | Yes, ECO Mode Efficiency > 96% |
Input | |
Input Type | Terminal Block |
Frequency Range | 45~65Hz |
Output | |
UPS Outlets (Numbers) | Terminal Block |
On Battery Output Voltage | Pure Sine Wave at 208, 220, 230, 240 Vac (Configurable) |
On Battery Output Voltage Distortion (@Nominal Battery Voltage) | < 2%(Linear Load), <5%(Non-Linear Load) |
On Battery Output Frequency | 50 Hz / 60 Hz (Auto-Sensing or Configurable) ± 0.5% |
Transfer Time (Typical) | 0ms |
Overload Protection |
Line Mode: 10 minutes minimum,then transfer to bypass @105% < Load≤125%; 1 minute minimum,then transfer to bypass @125 < Load≤150% ; 10 second minimum then transfer to bypass @Load>150%; 1 second minimum then transfer to bypass@Load>170%; Battery Mode: 2 minutes minimum,then shutdown @105% < Load≤125%; 30 sec minimum,then shutdown @125 < Load≤150% ; 1 second minimum then shutdown @Load>150%; |
Short Circuit Protection | UPS Output Cut off Immediately or Circuit Breaker Protection |
Surge Protection and Filtering | |
Surge Protection | Yes |
DSL/Phone/Fax/Modem protection | No |
Physical | |
Dimensions(H x W x D)(mm) | 708 x 260 x 550 |
Weight(kg) | 70 |
Battery | |
Sealed Maintenance Free Lead Acid Battery | (20) 12V / 7AH |
Typical Recharge Time | 6 |
Runtimes | |
Half load-Full load (mins) | 15/5 |
Status Indication | |
Indicators | Power On, Line Mode, Battery Mode, Bypass Mode, ECO Mode,C/F Mode, Fault, Replace Battery |
Audible Alarms | Battery Mode, Battery Low, Overload, UPS Fault, Replace Battery |
Communication | |
Power Management Software | PowerPanel® Business Edition |
Management | |
Self-Test | Yes |
Auto-Charge/Auto-Restart | Yes |
Auto-Overload Recovery | Yes |
Cold Start(DC Start) | Yes |
Connectivity Ports | (1) Serial Port (RS232), (1) USB Port, (1) EPO/ROO |
SNMP/HTTP Capable | Optional |